Range: Cooling Towers
DP-CAPH-RXPP (Bleed, Inhib, BioA, pH, ORP via CL2 + Br Pumps)
Convergent Water Controls | SKU:
DP-CAPH-RXPP
DP-CAPH-RXPP (Bleed, Inhib, BioA, pH, ORP via CL2 + Br Pumps) is backordered and will ship as soon as it is back in stock.
- Internet Based Connectivity as an option
- Monitoring and control of Conductivity/TDS, pH and ORP simultaneously
- On-board data logging
- Continuous readout of Conductivity, Temp, pH & ORP with each setpoint on backlit LCD
- Display and logging of cycles of concentration of the cooling tower
- Manual slug dose feature on all pumps
- Inhibitor modes: On bleed, After bleed, 24/7 cycle, Proportional to make-up
- Ability to measure and log cooling tower make-up and bleed water flow rate & consumption
- Inhibitor, Non-oxidising biocide, Chlorine & Bromine pumps. Ratio of Chlorine to Bromine is approx. 3:1.
- Disinfection feature to allow ORP control to a temporary high setpoint
- 28 Day Timers for disabling pH & ORP output if continuous control not desired.
- 28 Day Biocide Dosing programs (max 70 per week)
- Password protection
Specifications
Specifications
-
ConfigurationBackboard Mounted
-
Data LoggingIncluded
-
InputsConductivity Probe with Electrodes & 47K NTC, Flow Switch Contact, ORP Probe, pH Probe, Water Meter Pulse
-
IP RatingIP65
-
MaterialsPVC Manifold, Solenoid valves brass
-
Max Pressure / Temp2.7 bar @ 50°C
-
OutputsAlarm Relay, Bio A Pump Via Relay, Bleed Valve Via Relay, Inhibitor Pump Via Relay, Optional Dispersant Pump Via Relay, Optional pH Pump Via Relay, ORP Bromine Pump Via Relay, ORP Chlorine Pump Via Relay
-
Port Size20mm Solvent Weld
-
Remote CommsOptional Modem
-
Variables MeasuredConductivity, Flow Status, Flow Volume, ORP, pH, TDS, Temperature