DP-DCAPH-RXB-X/4S-CAB (Bleed, Inhib, BioA, pH GPOs for opt pumps

Convergent Water Controls  |  SKU: DP-DCAPH-RXB-X/4S-CAB

  • Digital controller & GPO's in hinged lockable, PC ABS cabinet, mounted with manifold on separate PVC back panel
  • Internet Based Connectivity as an option
  • Continuous readout of Conductivity, Temp, pH & ORP with each setpoint on backlit LCD
  • Monitoring and control of Conductivity/TDS, pH and ORP simultaneously
  • On-board data logging
  • Display and logging of cycles of concentration of the cooling tower
  • Manual slug dose feature on all pumps
  • Inhibitor modes: On bleed, After bleed, 24/7 cycle, Proportional to make-up
  • Ability to measure and log cooling tower make-up and bleed water flow rate & consumption
  • GPO's for Inhibitor, Non-oxidising biocide, pH, & Dispersant pumps
  • Disinfection feature to allow ORP control to a temporary high setpoint
  • 28 Day Timers for disabling pH & ORP output if continuous control not desired.
  • 28 Day Biocide Dosing programs (max 70 per week)
  • Password protection

Specifications

  • Configuration
    Controller & Pumps Mounted In Cabinet
  • Data Logging
    Included
  • Inputs
    Conductivity Probe with Electrodes & 47K NTC, Flow Switch Contact, ORP Probe, pH Probe, Water Meter Pulse
  • IP Rating
    IP65
  • Materials
    PVC Manifold, Solenoid valves brass
  • Max Pressure / Temp
    6.9 bar @ 25°C
  • Outputs
    Alarm Relay, Bleed Valve Via Relay, ORP Brominator Valve Via Relay, Switched GPOs for optional pumps/valves
  • Port Size
    20mm Solvent Weld
  • Remote Comms
    Optional Modem
  • Variables Measured
    Conductivity, Flow Status, Flow Volume, ORP, pH, TDS, Temperature